Tech Tip
Don't confuse amps and amp hours. Amp hours is a measure of battery capacity, amps is a measure of current. This is a heavy duty BMS capable of carry 1000 amps. It would typically be used in a super heavy duty system. Just because you have 1000 amp hours of batteries doesn't mean you have to use this BMS.
Power
Lynx Smart BMS 500A
Lynx Smart BMS 1000A
Supply voltage range
9 – 60Vdc
Supported system voltages
12, 24 or 48V
Reverse polarity protection
No
Main safety contactor continuous current rating
500A continuous
1000A continuous
Main safety contactor peak current rating
600A for 5 minutes
1200A for 5 minutes
Power consumption OFF mode
0.3mA for all system voltages
Power consumption in Standby mode
Approximately 0.6W (50mA at 12V)
Power consumption in ON mode
Approximately 2.6W (217mA at 12V) depending on the state of the relays
Approximately 4.2W (350mA at 12V) depending on the state of the relays
Minimum load resistance for pre-charging
10O and above for 12V systems
20O and above for 24V and 48V systems
AUX output maximum current rating
1.1A continuous, protected by resettable fuse
Allow-to-charge port maximum current rating
0.5A at 60Vdc, protected by resettable fuse
Allow-to-discharge port maximum current rating
Programmable relay (SPDT) maximum current rating
2A at 60Vdc
Connections
Busbar
M8 (Torque: 14 Nm)
M10 (Torque: 33 Nm)
(14Nm for units with a serial number before HQ2340XXXX)
VE.Can
RJ45 and RJ45 terminator
I/O
Removable multi-connector with screw terminals
Battery BMS cables
Male and female circular 3-pole connector with M8 screw ring
Up to 20 batteries can be connected to the BMS by daisy chaining them
Lynx Distributor (up to 4 modules)
RJ10 (cable ships with each Lynx Distributor)
Physical
Enclosure material
ABS
Enclosure dimensions (h x w x d)
190 x 180 x 80mm
230 x 180 x 100mm
Unit weight
1.9 kg
2.7 kg
Busbar material
Tinned copper
Busbar dimensions (h x w)
8 x 30mm
Environmental
Operating temperature range
-40°C to +60°
Storage temperature range
Humidity
Max. 95% (non-condensing)
Protection class
IP22
Standards
Safety
EN-IEC 63000:2018
EMC
EN-IEC 61000-6-3:2007/A1:2011/AC:2012
QMS
NEN-EN-ISO 9001:2015