MultiPlus-II 120V
24/5000/120-95
48/5000/70-95
PowerControl & PowerAssist
Yes
Transfer switch
95A
Maximum AC input current
INVERTER
DC Input voltage range
19 - 33V
38 - 66V
Output in inverter mode
Output voltage: 120VAC ± 2%
Frequency: 60Hz ± 0,1%
Continuous output power at 25°C (2)
5000VA
Continuous output power at 25°C
4000VA
Continuous output power at 40°C
3700VA
Continuous output power at 65°C
3000VA
Peak power
9000VA
Maximum efficiency
95%
96%
Zero load power
24W
19W
Zero load power in AES mode
10W
Zero load power in Search mode
3W
CHARGER
AC Input
Single phase: 90-140VAC 45-65Hz
Charge voltage 'absorption'
28.8V
57.6V
Charge voltage 'float'
27.6V
55.2V
Storage mode
26.4V
52.8V
Maximum battery charge current (3)
70A
Battery temperature sensor
GENERAL
Auxiliary output (4)
43A
48A
External AC current sensor (optional)
100A
Programmable relay (5)
Protection (1)
a – g
VE.Bus communication port
For parallel, split phase and three phase operation, remote monitoring and system integration
General purpose com. port (6)
Yes, 2x
Remote on-off
Operating temperature range
-40 to +60°C (-40 - 140°F) fan assisted cooling
Humidity (non-condensing)
max 95%