Tech Tip
This is one of our more complicated products. Take a look at the "additional information" tab first and then feel free to give us a call and have us talk you it if you need additional information. We are here to help. The manual suggests a 400 amp DC fuse for this unit.
Quattro-II
12/3000/120-50 2x120V
24/3000/70-50 2x120V
PowerControl & PowerAssist
Yes (on L1 input)
Transfer switch
50 A
Maximum AC input current
50 A (each leg)
INVERTER
DC Input voltage range
9.5 – 17 V
19 - 33 V
Output when in inverter mode
Output voltage: 120 VAC ± 2%
Frequency: 60 Hz ± 0.1% (1)
Cont. output power at 25°C (3)
3000 VA
Cont. output power at 25°C
2400 W
Cont. output power at 40°C
2200 W
Cont. output power at 65°C
1700 W
Maximum apparent feed-in power
2500 VA
Peak power
5500 W
Maximum efficiency
93%
94%
Zero load power
15 W
11 W
Zero load power in AES mode
10 W
8 W
Zero load power in Search mode
4 W
Maximum output current
60A peak, 50Arms for 1seconds
CHARGER
AC Input
Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
Charge voltage 'absorption'
14.4 V
28.8 V
Charge voltage 'float'
13.8 V
27.6 V
Storage mode
13.2 V
26.4 V
Maximum battery charge current (4)
120 A
70 A
Battery temperature sensor
Yes
GENERAL
Auxiliary output
Yes (50 A)
Programmable relay (5)
Protection (2)
a – g
VE.Bus communication port
For parallel and three phase operation, remote monitoring and system integration
General purpose communication port
Yes, 2x
Remote on-off
Operating temperature range
-40 to +65°C (-40 - 150°F) fan assisted cooling
Humidity (non-condensing)
max 95%
ENCLOSURE
Material & Colour
Steel, blue RAL 5012
Protection category
IP22
Battery-connection
2x2 M8 bolts
2 M8 bolts
120/240 V AC-connection
Screw terminals 21 mm² (4 AWG)
Weight
23.8 kg ( 52 lb)
22.5 kg (50 lb)
Dimensions (hxwxd) mm
579 x 319 x 168 mm
23 x 13 x 7 inch
STANDARDS
Safety
EN-IEC 60335-1, EN-IEC 60335-2-29
Emission, Immunity
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Can be adjusted to 50 Hz
Protection key:
output short circuit
overload
battery voltage too high
battery voltage too low
temperature too high
120 VAC on inverter output
input voltage ripple too high
Non-linear load, crest factor 3:1
Up to 75°F / 25°C ambient
Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating: 120V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC
A. o. to communicate with a Lithium-Ion battery BMS