Electrical
Input voltage range
9 – 70 Vdc
Current draw - regular operation
10 mA (excluding Load disconnect current)
Current draw - low cell voltage
2 mA
Current draw - switched off via remote on/off terminal
1,50 mA
GX-pow output
1 A
Aux-in input
Pre-alarm output current rating
1 A, not short circuit protected
Load disconnect output
Normally high (output voltage ˜ supply voltage – 1 V)
Floating when the load needs to be disconnected
Source current limit: 1 A
Sink current: 0 A
Charge disconnect output
Normally high, (output voltage ˜ supply voltage – 1 V)
Floating when charger should be disconnected
Source current limit: 10 mA
Remote on/off terminals
Usage modes to turn the system on or off:
ON when the L and H terminal are interconnected (switch or relay contact)
ON when the L terminal is pulled to battery minus (V<3,5 V)
ON when the H terminal is high (2,9 V < VH < Vbat)
OFF in all other conditions
VE.Bus communications ports
2 x RJ45 sockets to connect to all VE.Bus products